How to add a door in Lenel OnGuard

Add an LNL-X2220 (Mercury LP1502) panel, an LNL-1320 (MR52) reader interface, two readers, REX and strike in OnGuard System Administration, then test in Alarm Monitoring.

Last verified Oct 25, 2026 2 sources Suggest a correction
On this pageAdd the access panelAdd Reader 1 on the MR52Set OSDP, keypad and door timingAdd Reader 2Map door contact, REX and strikeCreate the timezone and access levelDownload and test in Alarm MonitoringTroubleshootingSourcesFAQs

OnGuard names Mercury hardware with Lenel part numbers. The LP1502 controller is the LNL-X2220 and the MR52 reader interface is the LNL-1320. (S1) The steps are the same in OnGuard 7.x and 8.x. OnGuard 8.3 adds Mercury M-Series and IP client connections.

Add the access panel

Flag
  1. Open Access Panels. In System Administration, go to Access Control > Access Panels.
  2. Pick the panel type and click Add. Use LNL-X2220 for a Mercury LP1502, or LNL-2220 for an EP1502. (S1)
  3. Fill the Location tab. Name the panel for its location, check Online, and enter the controller's IP address as the primary connection.
FieldSet to
Panel typeLNL-X2220 (Mercury LP1502) (S1)
OnlineChecked
Primary connectionIP address of the LP1502

Add Reader 1 on the MR52

Flag

In OnGuard the MR52 is the reader Type LNL-1320, not a separate device. (S1) Both readers share the board's address and differ by Reader Number.

  1. Go to Access Control > Readers and Doors and click Add.
  2. Set Type to LNL-1320 (Dual Interface). That is the MR52. (S1)
  3. Enter the port, the address and Reader Number 1. The address matches the DIP switches on the MR52. (S2)
  4. Set the reader output and card format. Match the reader's protocol (OSDP or Wiegand) and the card format on the site's badges. (S2)
FieldSet to
TypeLNL-1320 (Dual Interface) = MR52 (S1)
AddressThe MR52 DIP switch address (S2)
Reader Number1
OutputOSDP or Wiegand, matching the reader (S2)
Card formatThe format on the site's badges

Set OSDP, keypad and door timing

Flag
FieldSet to
OSDP addressThe address set on the reader
Secure ChannelOn only when the reader is set for Secure Channel (S2)
KeypadNone when the reader has no keypad
Strike modeFail-safe or fail-secure, matching the lock (S2)

Strike time and held-open time are entered in seconds.

Add Reader 2

Flag
  1. In Readers and Doors, click Add again.
  2. Use the same LNL-1320 address with Reader Number 2.
  3. Pair it with Reader 1 so both readers control one door.

Map door contact, REX and strike

Flag

The LNL-1320 has door contact supervision, a REX input and a strike output on each door. (S2)

FieldSet to
Door contactLNL-1320 door contact input (S2)
REXLNL-1320 REX input (S2)
Strike relayLNL-1320 strike output (S2)

Create the timezone and access level

Flag
  1. Go to Access Control > Timezones. Make a timezone or reuse one, such as Always.
  2. Go to Access Levels. Make an access level that includes the new entry and exit readers.
  3. Assign the level to a test badge.

Download and test in Alarm Monitoring

Flag
  1. Download the panel from Alarm Monitoring > System Status.
  2. Use Open Door(s) to fire the strike.
  3. Present the test badge and confirm access granted on both readers.
  4. Press the REX and confirm it releases the strike without a Door Forced alarm.
  5. Hold the door past the held-open time and confirm the Door Held alarm.
  • MR52 DIP address matches the Address field
  • MR52 baud matches the panel downstream port
  • OSDP termination is on the last device
  • Reader protocol matches the reader
  • Card format matches the badges
  • Panel downloaded after the changes
  • Grant, REX, forced and held were tested

Troubleshooting

Flag

Sources

  1. S1Genetec TechDocs: Comparison chart for Mercury and Lenel model numberstechdocs.genetec.com · pulled Oct 25, 2026
  2. S2LenelS2 LNL-1320 Series 3 Dual Reader Interface Module datasheet2024/06 · www.lenels2.com · pulled Oct 25, 2026

FAQs

How do you add an MR52 in OnGuard?

The MR52 is not its own object in OnGuard. Add it as reader Type LNL-1320 on Readers and Doors. The LP1502 is the LNL-X2220 and the EP1502 is the LNL-2220. (S1)

Why will a Mercury-branded board not come online?

Mercury-branded boards can be blocked by the OnGuard license OEM mask. OnGuard expects LNL-branded boards.