HES 9600 · 1 of 1 · Image: HES
| 9400|9500|9600|9700|9800 Electric Strike Installation Instructions & Frame Preparation | 9400|9500|9600|9700|9800 Electric Strike Installation Instructions & Frame Preparation (AADSS1053638 © 2024 (PDF Apr 2024)) |
No reviews yet.
Distribution
| Voltage | 12 or 24 VDC continuous duty |
|---|---|
| Current | 500 mA @12 V, 250 mA @24 V |
| Resistance | 24 Ω @12 V, 96 Ω @24 V |
| Tolerance | ±10% |
| Wire gauge | 12 V: 18 ga ≤200 ft, 16 ga 200–400 ft; 24 V: 22 ga ≤300 ft, 20 ga 300–400 ft (round trip) |
| UL 1034 | 1500 lb static, 70 ft-lb dynamic, 250,000 cycles |
Verify input voltage with a meter first; >10% over rating can damage the solenoid
Fail safe negates the fire rating; don't use fail safe in fire-rated or windstorm applications
Switch states listed for an unpowered strike with the monitor unactuated (door open)
When converting LBSM to fail safe, move the monitoring switch position too