End-of-Line Resistor Values for Alarm Panels and Access Control: Field Guide
Which end-of-line resistor each common alarm panel and access controller expects, how to wire it, and how to find it on a takeover.
On this page
How EOL supervision worksQuick reference by panelHoneywell / Resideo VISTA-15P and VISTA-20PDSC PowerSeries and PowerSeries NeoBosch B Series (B3512, B4512, B5512, B6512)DMP XR150 / XR550Elk M1Interlogix / GE NetworX NX-8Napco Gemini2GIG GC3 / EDGEQolsys IQ Hardwire 16-FAccess control inputsResistor color band chart (4-band, 5%)What to stock in the truckTroubleshootingRelated toolsSourcesFAQsEvery supervised zone or door input needs the right end-of-line (EOL) resistor. Put the wrong value in and the panel shows a trouble, a fault or a zone that never restores. This guide lists the values the manufacturers' manuals specify for the panels and controllers techs run into most, and shows how to work out an unknown one on a takeover.
How EOL supervision works
The panel puts a small voltage on the loop and reads the resistance back. With a resistor at the far end, it can tell three states apart: normal (it sees the resistor), open (cut wire or open NC contact) and short (shorted wire or closed NO contact).
- NC (normally closed), single EOL: contacts in series. The resistor goes in series after the last device. (S1)
- NO (normally open), single EOL: contacts in parallel. The resistor goes across the loop at the last device. (S1)
- DEOL (dual end-of-line): one resistor across the contact and one in series at the end of the line. The panel can now tell an alarm apart from a cut wire or a short, which it reports as tamper. (S3, S6)
- Zone doubling: two contacts on one loop, each with a different resistor value, so one pair of terminals reports as two zones. (S1, S11)
Quick reference by panel
| Panel | Zone EOL | DEOL / zone doubling | Fire / 2-wire smoke | Bell / siren | Source |
|---|---|---|---|---|---|
| Honeywell/Resideo VISTA-15P / 20P | 2k (zone 1 must use an EOL) | Zone doubling (20P only): 3k + 6.2k | 2-wire smokes on zone 1 only, EOL across the last detector | Not confirmed | S1, S2 |
| DSC PowerSeries Neo (HS2016–HS2128) | 5.6k | 5.6k + 5.6k | Fire and 24-hr supervisory zones: single EOL only | 1k across Bell+/Bell- if unused | S3, S4 |
| DSC PowerSeries PC1864 | 5.6k | 5.6k + 5.6k | 2-wire smoke on PGM2: 2.2k across the last detector | 1k if unused | S5 |
| Bosch B3512/B4512/B5512/B6512 | 1k (ICP-1K22AWG-10) | 1k + 1k (Circuit Style = Dual) | No onboard NAC; D192G with 1k EOL | Through D192G | S6, S7 |
| DMP XR150/XR550 | 1k (DMP 311), can be set to 2.2k | Not covered here | Zones 9–10 are 2-wire powered zones: 3.3k (DMP 309) | 1k, 1/2 W across the bell circuit | S8 |
| Elk M1 | 2.2k | Not covered here | Zone 16 2-wire smoke: 680 Ω (move JP1) | Not covered here | S9 |
| Interlogix/GE NetworX NX-8 | 3.3k | DEOL 3.3k + 3.3k; zone doubling 3.74k + 6.98k | 2-wire smoke loop ≤ 30 Ω | Not covered here | S11 |
| Napco Gemini | 2.2k | Not covered here | Not covered here | Not covered here | S12 |
| 2GIG GC3 / EDGE (hardwire zones) | 2.2k | Not covered here | Not covered here | Not covered here | S13 |
| Qolsys IQ Hardwire 16-F | 4.7k (learn mode accepts 1k–10k; zone 16 stays 4.7k) | Not covered here | Not covered here | Not covered here |
"Not covered here" means the source we used didn't give a value. It doesn't mean the panel lacks the feature.
Honeywell / Resideo VISTA-15P and VISTA-20P
- Zone EOL: 2k. Zones can be programmed as NC, NO, NC-EOL or NO-EOL using the Hardwire Type prompt in zone programming. Zone 1 is EOL only. UL commercial burglary installs must use EOL zones. (S1)
- Zone doubling (20P only): Hardwire Type option 3. Use 3k and 6.2k, 5%, 1/4 W or larger (supplied with the panel). Zones pair 2/10, 3/11 and so on up to 8/16. Don't zone-double fire zones. A short across either zone of a doubled pair shows as a tamper (CHECK). (S1)
- 2-wire smoke: zone 1, terminals 8 (+) and 9 (–). Up to 16 detectors, or 10 with Clean Me. EOL resistor across the loop at the last detector. (S1, S2)
- 4-wire smoke: zones 2–8. Use a relay (4204/4229) or trigger 17 programmed as zone type 54 to reset power. (S2)
- Bell supervision resistor, VISTA-21iP, VISTA-128/250: Not confirmed. Check that model's manual.
DSC PowerSeries and PowerSeries Neo
- Zone EOL: 5.6k. Single EOL, DEOL (5.6k + 5.6k) or NC with no EOL are set in programming. (S3, S5)
- Fire and 24-hour supervisory zones: single EOL only, never DEOL. (S3)
- Bell: the output is supervised. If no siren is connected, put 1k across Bell+ and Bell- or the panel will show a trouble. (S3, S4)
- PC1864 2-wire smoke: program PGM2 for 2-wire smokes. Connect detector + to AUX+ and – to PGM2, and put 2.2k across the last detector. Don't use 5.6k here. (S5)
- PC1616/1832, PC1555/PC585: Not confirmed in this guide. They're commonly 5.6k, but check the manual.
Bosch B Series (B3512, B4512, B5512, B6512)
- Zone EOL: 1k, part ICP-1K22AWG-10 (brown-black-red). 1k resistors ship with the panel. Wire and contact resistance, not counting the EOL, has to stay at 100 Ω or less. (S6)
- DEOL: set Point Profile > Circuit Style to Dual. Put one 1k at the device and one 1k at the end of the line. (S6, S7)
- Unused points (Point Profile 0) don't need a resistor. (S6)
- NAC: no onboard NAC. Use a D192G with a 1k EOL (P/N F01U033966). (S7)
- GV4/D9412 and Solution 2000/3000: Not confirmed. Check the manual.
DMP XR150 / XR550
- Zones 1–8: 1k EOL (DMP Model 311) by default. You can change it to 2.2k in System Options when taking over an existing panel. (S8)
- Zones 9–10: 2-wire powered zones with reset, 3.3k EOL (DMP 309). (S8)
- Bell: add 1k, 1/2 W across terminals 5–6 for supervision when using a horn or siren. (S8)
Elk M1
- Zone EOL: 2.2k. (S9)
- 2-wire smoke on zone 16: move JP1, program Wire Type 6, and use the 680 Ω EOL from the hardware pack instead of the 2.2k. Maximum wire resistance is 60 Ω. (S9)
Interlogix / GE NetworX NX-8
- Zone EOL: 3.3k. (S11)
- DEOL: enable it in System Options and use two 3.3k resistors per zone. (S11)
- Zone doubling: the NX-200 kit has 3.74k and 6.98k resistors. (S11)
- Loop resistance: 300 Ω maximum on a standard loop, 30 Ω on 2-wire smokes. (S11)
- GE Concord: Not confirmed.
Napco Gemini
- Zone EOL: 2.2k per supervised hardwired zone. (S12)
2GIG GC3 / EDGE
- Hardwire zones: 2.2k at the far end of the loop, with the zone programmed as EOL. (S13)
Qolsys IQ Hardwire 16-F
- Standard: 4.7k. Newer modules have a legacy/learn mode that accepts 1k–10k, which helps on takeovers. Zone 16 stays 4.7k.
Access control inputs
| Controller | Door contact / REX supervision | Notes | Source |
|---|---|---|---|
| HID Mercury LP1502 (LenelS2 and other Mercury-based systems) | 1k + 1k, 1%, 1/4 W | Mount the resistors close to the sensor. Custom values can be set in the host software. | S15 |
| Software House iSTAR | 1k dual EOL | 1k reads secure. 500 Ω or 2k reads alert. Over 30k reads open. | S16 |
| Brivo ACS6000 series | 2k + 2k | One in parallel with the switch, one in series, near the switch | S17 |
| Keyscan CA4500 | 1k single, or 1k/3k dual | Selected by jumper J18. All inputs on the board share the setting. | S18 |
| Kantech KT-400 | 5.6k (none, single or double, set in EntraPass) | The 1k resistors in the kit go across +/LK- on unused lock outputs, not on inputs. | S19 |
Not confirmed: Genetec Synergis, Honeywell Pro-Watch/WIN-PAK, AMAG, Paxton, Avigilon Alta (Openpath) and Verkada. Many of these run on Mercury hardware, so 1k/1k is likely, but check the controller's manual. For a fire alarm interface, the fire panel usually supplies a dry relay contact to the controller input or the lock power. Supervise it the way that controller's inputs are supervised, and follow local code and the AHJ.
Resistor color band chart (4-band, 5%)
| Value | Bands | Where you'll see it |
|---|---|---|
| 680 Ω | blue-gray-brown | Elk zone 16 smoke |
| 1k | brown-black-red | Bosch, DMP, Mercury, iSTAR, Keyscan, DSC bell, DMP bell |
| 2k | red-black-red | VISTA, Brivo |
| 2.2k | red-red-red | Elk, Napco, 2GIG, DMP takeover option, DSC PGM2 smoke |
| 3k | orange-black-red | VISTA zone doubling |
| 3.3k | orange-orange-red | NetworX, DMP powered zones |
| 4.7k | yellow-violet-red | Qolsys IQ Hardwire 16-F |
| 5.6k | green-blue-red | DSC, Kantech |
| 6.2k | blue-red-red | VISTA zone doubling |
The fourth band is tolerance: gold is 5%. Read from the end opposite the gold band.
What to stock in the truck
This list is based on how many panels and controllers in this guide use each value. It isn't a market-share ranking.
- 1k (and 1k 1/2 W for bell circuits)
- 2.2k
- 5.6k
- 2k
- 4.7k
- 3.3k
- Specialty: 680 Ω, 3k + 6.2k (VISTA doubling), 3.74k + 6.98k (NX-200)
Troubleshooting
- Measure the loop: disconnect the zone at the panel and meter across the pair with the device closed and the door shut. You should read the EOL value plus a little wire resistance. Open the device and check the reading changes the way it should: open for NC-EOL, near 0 for NO-EOL, or about double for DEOL in alarm.
- Reading about 0 Ω: a short, or the resistor is at the panel or across an NC contact by mistake.
- Reading infinite (OL): a broken wire, a missing resistor or an open contact.
- Reading about twice the expected value: you're probably on a DEOL loop (two resistors in series).
- Takeover with unknown resistors: meter every loop before you pull the old panel. Then either set the new panel to match (DMP allows 2.2k, Qolsys 16-F learn mode accepts 1k–10k, Mercury allows custom EOL in software (S8, S15)) or replace the resistor at the last device.
- Resistor found inside the panel can: move it to the last device, or the run isn't supervised. (S1)
- High loop resistance: stay under the panel's limit: 100 Ω on Bosch (not counting the EOL) and 300 Ω on NetworX. (S6, S11)
Related tools
- Resistor decoder: read color bands, check a meter reading against the loop, and look up the EOL value by panel
Sources
- Honeywell/Ademco VISTA-15P/20P Installation and Setup Guidesafehomecentral.com · pulled Oct 24, 2026
- Resideo VISTA-15P/20P Smoke Detector Wiring (GeoArm support copy of install manual)support.geoarm.com · pulled Oct 24, 2026
- DSC PowerSeries Neo HS2016/2032/2064/2128 Reference Manualwww.dsc.com · pulled Oct 24, 2026
- DSC PowerSeries Neo Installation Guide, Bell Wiring (Johnson Controls docs)docs.johnsoncontrols.com · pulled Oct 24, 2026
- DSC PowerSeries PC1864 Installation Manualcms.dsc.com · pulled Oct 24, 2026
- Bosch B6512/B5512/B4512/B3512 Installation Manualkeenfinity.blob.core.windows.net · pulled Oct 24, 2026
- Bosch B5512/B4512/B3512 UL Installation Manualresources.keenfinity.tech · pulled Oct 24, 2026
- DMP XR150/XR550 Series Installation Guide (ManualsLib copy)www.manualslib.tech · pulled Oct 24, 2026
- Elk M1 Installation Manual, Two-Wire Smoke Zones (ManualsOnline copy)www.manualsonline.com · pulled Oct 24, 2026
- NX-8 Control Panel Installation Manual Rev P (NX-200 kit)islandsecurity.com · pulled Oct 24, 2026
- Napco Technical Library FAQ 2052tech.napcosecurity.com · pulled Oct 24, 2026
- 2GIG EDGE Installation Guide2gig.com · pulled Oct 24, 2026
- HID Mercury LP1502 Controller Installation and Specificationswww.mercury-security.com · pulled Oct 24, 2026
- Software House iSTAR Edge Installation & Quick Start Manual, p. 18www.manualslib.com · pulled Oct 24, 2026
- Brivo ACS6100 Installation Guideresources.brivo.com · pulled Oct 24, 2026
- Keyscan VII Technical Guidecdn.smartbuildtechnology.com · pulled Oct 24, 2026
- Kantech EntraPass KT-400 Installation Manualentrapass.com · pulled Oct 24, 2026
FAQs
What EOL resistor does a VISTA-20P use?
2k. 2-wire smokes go on zone 1 with the EOL across the last detector. (S1, S2)
What resistor goes on a DSC bell output with no siren?
1k across Bell+ and Bell-. (S3, S4)
Is Bosch B Series 1k or 2.2k?
1k (ICP-1K22AWG-10), and DEOL also uses 1k + 1k. (S6)
Can I keep 2.2k resistors when I swap to a DMP panel?
Yes. XR150/XR550 zones 1–8 can be set to 2.2k in System Options. (S8)
What does Mercury want on door contacts and REX?
1k + 1k, 1%, close to the device. Custom values can be set in the host software. (S15)
Why do my Kantech inputs show trouble with 1k resistors?
KT-400 inputs use 5.6k. The 1k resistors in the kit are for unused lock outputs. (S19)