How do I fix a communicator, phone line or comm fault trouble on a Fire-Lite MS-9200UDLS
A TELCO LINE or COMM FAULT trouble on the Fire-Lite MS-9200UDLS means the onboard DACT lost a supervised phone line or could not deliver a report. Check that each line comes in through its own RJ31X jack with the panel as the first device on the line, that the line type (touchtone or rotary) is programmed correctly, and that Phone Line 2 supervision matches how the second path is really provided. Watch the Kiss-off LED to confirm the central station acknowledges each message.
Steps
From: MS-9200UDLS Series manual, pp. 37, 119, 125, 135, 150
- Check the wiring pathTwo independent telephone lines connect through RJ31X jacks. The panel's digital communicator must be the first device on the incoming telephone circuit, ahead of premise phones, fax machines and answering systems.
- Check the jacks and cableEach line plugs into the PRI. PHONE LINE and SEC. PHONE LINE connectors with the 7 foot MCBL-7 cable. Remove the shorting bars inside the RJ31X jack during installation.
- Don't dial a forwarded numberThe DACT must not be used to dial a phone number that is call-forwarded.
- Confirm the DACT is enabled and the line type is rightIn programming open Option Modules, 2 for On Board DACT. Set Enabled to Yes, then set Primary Phone and Secondary Phone to Touchtone, Rotary 67/33 or Rotary 62/38 to match the line.
- Match Phone Line 2 supervision to the installIf the second path is an alternate means of transmission and not a second phone line, set Supervise Phone Line 2 to No on On Board DACT Screen #2. The factory default is supervised.
- Read status without changing anythingRead Status Screen #4, 2 for Phone Line shows the line types and whether Phone Line 2 is supervised; 3 for Central Station shows reporting enabled, Primary and Secondary, and the Call Limit for DACT trouble calls within a 24 hour period.
- Test and watch the Kiss-off LEDThe green Kiss-off LED blinks when the central station acknowledges each transmitted message. The red Primary and Secondary Line Active LEDs show which line is in use.
Specs & limits
From: MS-9200UDLS Series manual, pp. 37, 119, 124-125
| TELCO LINE 1 | Contact ID 351 |
|---|---|
| TELCO LINE 2 | Contact ID 352 |
| COMM FAULT 1 and 2 | Contact ID 354 |
| Line jack | RJ31X, one per line |
| Phone types | Touchtone, Rotary 67/33, Rotary 62/38 |
| Phone Line 2 supervision | Supervised by factory default |
Common mistakes
From: MS-9200UDLS Series manual, pp. 37-38, 124-125
- Premise phones or a fax ahead of the panel. The DACT can't seize the line unless it is the first device on the circuit.
- Leaving Phone Line 2 supervised when the second path is a radio or IP communicator. The panel reports a TELCO LINE 2 trouble that never clears.
- Missing ferrite clamps. FCC requirements call for one clamp on each phone line inside the cabinet.
Applies to
MS-9200UDLS · Series manual P/N 52750:M
Sources
- MS-9200UDLS Series Manual, p. 37 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 119 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 124 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 125 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 150 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 135 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 38 (52750 Rev M)