How do I calculate battery size for a Fire-Lite MS-9200UDLS fire alarm panel
For the Fire-Lite MS-9200UDLS, list every device's standby and alarm current in Table 7.3, multiply the battery-powered standby load by 24 hours and the alarm load by the alarm time (0.084 for 5 minutes), add the two ampere-hour figures, then multiply by the 1.2 derating factor. The result is the battery size in AH. The panel charges and houses batteries from 7 AH to 18 AH; bigger sets need an external charger and cabinet.
Steps
From: MS-9200UDLS Series manual, pp. 162-163
- List every powered deviceIn Table 7.3 with its quantity. Start with the main circuit board, which draws 0.275 A in alarm and 0.145 A in standby on battery, then add annunciators, relay and LED modules, the 4XTMF, 4-wire detector heads and power supervision relays.
- Add the SLC devicesEach addressable detector and module has its own standby current in the table, for example 0.00030 A for most detector heads and 0.00040 A for an MMF-300 monitor module.
- Add the NAC loadEnter the alarm current of the horns and strobes on NAC #1 to NAC #4. These draw only in alarm, so they go in the fire alarm load column, not standby.
- Total the columnsCalculation Column 2 is the battery-powered fire alarm load and Column 3 is the battery-powered standby load. Copy both totals to Table 7.4.
- Multiply by the required timesStandby load times 24 hours. Alarm load times 0.084 for 5 minutes of alarm, or 0.168 for 10 minutes. NFPA 72 Local, Proprietary, Central, Auxiliary and Remote systems require 24 hours of standby followed by 5 minutes in alarm.
- Add and derateAdd the standby and alarm ampere-hours, then multiply the sum by the derating factor of 1.2. That is the battery size in AH.
- Pick and label the batteriesUse sealed lead acid batteries that meet or exceed the calculated AH, and write the requirement on the Protected Premises label inside the cabinet door.
Specs & limits
From: MS-9200UDLS Series manual, pp. 17, 162-163
| Standby time | 24 hours |
|---|---|
| Alarm time multiplier | 0.084 for 5 minutes, 0.168 for 10 minutes |
| Derating factor | 1.2 |
| Charger and cabinet range | 7 AH to 18 AH in the panel cabinet |
| Total panel load | 3.0 amps with one transformer, 6.0 amps with the optional XRM-24B(E) |
| Per NAC | 2.5 amps max per circuit |
Common mistakes
From: MS-9200UDLS Series manual, pp. 162-163
- Putting NAC current in the standby column. Horns and strobes only draw in alarm, so their current belongs in the alarm column.
- Forgetting the 1.2 derating factor. Without it the battery is undersized as it ages.
- Planning batteries larger than 18 AH in the panel cabinet. Larger batteries need a UL listed external battery charger and cabinet such as the BB-26 or BB-55F.
Applies to
MS-9200UDLS · Series manual P/N 52750:M
Also asked as: “how to size fire panel batteries”
Sources
- MS-9200UDLS Series Manual, p. 162 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 163 (52750 Rev M)
- MS-9200UDLS Series Manual, p. 17 (52750 Rev M)