HES 1006 · 1 of 1 · Image: HES
| HES 1006 Series Electric Strike Installation Instructions | HES 1006 Series Electric Strike Installation Instructions (AADSS1009170 © 2025 (PDF Mar 2025)) |
No reviews yet.
Distribution
Market
| Current | .48 A @12 VDC, .24 A @24 VDC continuous |
|---|---|
| Resistance | 25 Ω @12 V, 100 Ω @24 V |
| Tolerance | ±10% |
| Wire gauge | 12 V: 18 ga ≤200 ft, 16 ga 200–300 ft, 14 ga 300–400 ft; 24 V: 18 ga ≤300 ft, 16 ga 300–400 ft (round trip) |
| Monitor rating | 500 mA @ 30 VDC |
Lead colours/joins differ from the HES 9600 family; do not reuse 9600 wiring
Switch states listed for strike keeper closed and LBM unactuated (door open)
Verify supply with a meter; >10% over rating can damage solenoid
No discussions tagged to this part yet.