How do I wire smoke detectors to a conventional fire alarm panel like the Fire-Lite MS-5UD
On a Fire-Lite MS-5UD (five zones) or MS-10UD (ten zones), each Initiating Device Circuit is Class B: loop the wire from the panel through every detector and put the 4.7 KΩ, ½ watt end-of-line resistor (P/N 71252) after the last device. 2-wire 24 VDC smoke detectors run on the zone pair alone. 4-wire smoke detectors also need the panel's resettable 24 VDC 4-wire smoke power (500 mA) and a UL listed power supervision relay at the end of the run.
Steps
From: MS-5UD & MS-10UD Series manual, pp. 24-25, 27, 55
- Confirm the devices are compatibleEach IDC accepts i3 smoke detectors, normally-open contact devices and conventional 2-wire or 4-wire 24 VDC smoke detectors listed in the Fire-Lite Device Compatibility Document.
- Run the zone as Class BTake the pair from the zone terminals to each detector in turn, in and out of every base. Each circuit is Style B (Class B) and is supervised for opens, shorts and ground faults.
- Install the end-of-line resistorAt the last device: 4.7 KΩ, ½ watt, P/N 71252. Put a 4.7 KΩ, ½ watt dummy load (P/N 71245) on every unused circuit.
- For 4-wire detectors, add powerTake resettable 24 VDC 4-wire smoke detector power (500 mA maximum, terminals 3 and 4) to every detector, and end the power run on a UL listed power supervision relay so a broken power wire shows as a trouble.
- Check loop resistanceThe maximum loop resistance for each IDC is 100 ohms, or 700 ohms per zone for linear heat detection.
- Program the zone typeIn Edit Input Zone Screen #2 press 2 for Type and pick 2-Wire Detector, Fire, Pull Station, Waterflow or another type. A 2-wire detector zone causes a fire alarm.
- Test each zoneBy opening the circuit for a trouble, then alarming one detector and resetting.
Specs & limits
From: MS-5UD & MS-10UD Series manual, pp. 24-25, 27, 31
| Zones | MS-5UD five IDCs, MS-10UD ten IDCs |
|---|---|
| IDC style | Style B (Class B); Style D (Class A) with the CAC-5X |
| End-of-line resistor | 4.7 KΩ, ½ watt, P/N 71252 |
| Loop resistance | 100 ohms max per IDC |
| 4-wire smoke power | 24 VDC resettable, 500 mA |
| Aux power jumper | JP31 pins 1 & 2 nonresettable, pins 2 & 3 resettable |
Common mistakes
From: MS-5UD & MS-10UD Series manual, pp. 24, 27, 31
- Putting 2-wire smoke detectors on a zone used for linear heat detection. The manual says not to.
- Feeding 4-wire detectors from nonresettable power. They latch in alarm and won't reset; use the resettable 4-wire smoke terminals.
- With a CAC-5X installed, a zone you want to keep Class B is wired only to the B+ and B- terminals with the end-of-line resistor after the last device. Don't also wire the A+ and A- terminals on the CAC-5X.
Applies to
MS-5UD · Manual 52626 rev C7MS-10UD
Also asked as: “how to wire smoke detectors to conventional facp”
Sources
- MS-5UD & MS-10UD Series Manual, p. 24 (52626 Rev C7)
- MS-5UD & MS-10UD Series Manual, p. 25 (52626 Rev C7)
- MS-5UD & MS-10UD Series Manual, p. 27 (52626 Rev C7)
- MS-5UD & MS-10UD Series Manual, p. 55 (52626 Rev C7)
- MS-5UD & MS-10UD Series Manual, p. 31 (52626 Rev C7)