Altronix AL400M220 · 1 of 1 · Image: Altronix
Key specs
| Input | Input 220VAC, 60Hz, 1.2A.; Input fuse rated @ 3.5A/250V.; Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C. supervised trigger input and polarity reversal trigger input. |
|---|---|
| Output | 12VDC or 24VDC selectable outputs.; 12VDC @ 4A or 24VDC @ 3A supply current.; Five (5) (auto-resettable) PTC protected outputs, rated @ 2A.; Output relay energizes when unit is triggered (form "C" contact rated 1A @ 28VDC).; Filtered and electronically regulated output.; Short circuit and thermal ov |
| Supervision | AC fail supervision (form "C" contacts).; Low battery supervision (form "C" contacts).; Battery presence supervision (form "C" contacts).; Power fail supervision relay (form "C" contacts). |
| Temperature | Operating: 0° C to 49° C (32° F to 120° F).; Storage: - 20° C to 70° C ( - 4° F to 158° F).; Relative Humidity: 85% +/- 5%.; 12VDC: 25 BTU/Hr.; 24VDC: 37 BTU/Hr.; System AC input VA requirement: 176VA. |
| Battery Charging | Built-in charger for sealed lead acid or gel type batteries.; Automatic switch over to stand-by battery when AC fails.; (Batteries are sold separately). |
| BTU/Hr. (approx.) | 12VDC: 25 BTU/Hr.; 24VDC: 37 BTU/Hr. |
| Visual Indicators | AC input and DC output LED indicators (power supply board).; Red LEDs indicate condition of power outputs (multi-output board).; Power & input trigger LEDs (multi-output board). |
Where to buy
No retail prices for AL400M220 yet.Check retailers
Documents
Guides that use this part
No guides tag this part yet.Browse guides
Contractors certified on Altronix
Find Contractors who list a Altronix certification.Find Contractors
Q&A and reviews
Discussions 0 tagged
No discussions tagged to this part yet.
Reviews
No reviews yet.
Max 4. Remove one.
Compare now