Can low voltage cable share a box, raceway or conduit with high voltage wiring
Generally no. Class 2 and Class 3 cabling, communications cable and power-limited fire alarm cable must stay out of boxes, raceways and enclosures that hold electric light, power or Class 1 conductors, unless a listed barrier or a permitted exception separates them. The rules are in NEC 725.136 for Class 2 and Class 3 circuits, 800.133 for communications, 760.136 for power-limited fire alarm and 820.133 for coax CATV.
Steps
- Identify the circuit classAccess control, intrusion and most camera power supplies are Class 2 or Class 3. Network, phone and data cable is communications. Fire alarm wiring from a listed panel is usually power-limited fire alarm (PLFA). Coax video is CATV/radio distribution.
- Find the governing sectionClass 2 and Class 3 separation is NEC 725.136. Communications is 800.133. PLFA is 760.136. Coax is 820.133. Each covers raceways, cable trays, boxes and enclosures.
- Keep separate raceways and boxesAs the default design. Run low voltage in its own conduit, sleeve or J-hook path and use separate back boxes or a two-gang box with a listed divider.
- Use a listed barrier where the code allows a shared enclosureMulti-gang boxes and enclosures with a permanent, listed barrier keep the low voltage compartment separate from line voltage terminations.
- Respect separation in open runsThe same sections require spacing between exposed low voltage cable and power conductors unless the power wiring is in a raceway or cable armor, or a fixed nonconductor is in between. Check the spacing value in your adopted edition.
- Follow the manufacturer tooEquipment manuals often add their own rule. DoorKing, for example, tells you to keep entry system wires a minimum of 18 inches from high voltage wires to prevent hum, which is stricter than many code minimums.
- Confirm with the AHJBefore rough-in on a commercial job, because the adopted NEC edition and local amendments decide which exceptions apply. See also this related page.
Specs & limits
| Class 2 and Class 3 | NEC 725.136 |
|---|---|
| Communications | NEC 800.133 |
| Power-limited fire alarm | NEC 760.136 |
| Coax CATV | NEC 820.133 |
Common mistakes
- Pulling a Cat6 through an existing power conduit because there is room. Fill is not the issue; mixing circuit classes is.
- Landing a relay that switches 120 V in the same compartment as Class 2 wiring with no barrier. Use a separate enclosure or a listed divider.
- Assuming low voltage means no code applies. Articles 725, 760, 800 and 820 all have installation rules.
Applies to
Also asked as: “can cat6 run with electrical”