Test
To conduct Walk Test on DMP CellComSL or Universal Alarm Communicator: reset by pressing RESET button, then enter 8144 at keypad.
Steps
From: DMP LT-1339 Programming guide: INSTALLAT programming guide, p. 36
- Conduct within 30 min of reset; ends after 20 min no trips or manual ENDSource: DMP LT-2539 Programming guide: INSTALLAT programming guide · p. 29 Source: DMP LT-2539 Programming guide: INSTALLAT programming guide · p. 29
- Sends Test Begin/End reports if monitored; displays TRIPS: XXX, TEST END WARNING at 5 min remaining, then Verify/Fail per zoneSource: DMP LT-2539 Programming guide: INSTALLAT programming guide · p. 29 Source: DMP LT-2539 Programming guide: INSTALLAT programming guide · p. 29
- Failed zones display as ZONE: XX -FAIL; faulted PN/SV zones send troubleSource: DMP LT-2539 Programming guide: INSTALLAT programming guide · p. 29 Source: DMP LT-2539 Programming guide: INSTALLAT programming guide · p. 29
Applies to
LT-1339
Sources
- DMP LT-1339 Programming guide: INSTALLATION AND PROGRAMMING GUIDE CELLCOMSL™ SERIES UNIVERSAL ALARM COMMUNICATOR FCC NOTI (LT-1339), p. 36, p. 36
- DMP LT-2539 Programming guide: INSTALLATION AND PROGRAMMING GUIDE Universal Alarm Communicator Digital Monitoring Product (LT-2539), p. 29, p. 29
- DMP LT-2539 Programming guide: INSTALLATION AND PROGRAMMING GUIDE Universal Alarm Communicator Digital Monitoring Product (LT-2539), p. 29, p. 29
- DMP LT-1339 Programming guide: INSTALLATION AND PROGRAMMING GUIDE CELLCOMSL™ SERIES UNIVERSAL ALARM COMMUNICATOR FCC NOTI (LT-1339), p. 36, p. 36