Dmp XT75 keypad bus wiring
DMP XT75 keypad bus lands on panel terminals RED , YEL , GRN , and BLK .
Steps
From: DMP XT75 Programming guide: INSTALLATION programming guide, pp. 7, 11, 13, 15
- Use 18- or 22-gauge unshielded wireDo not use twisted pair or shielded wire on keypad bus data.
- 22-gauge keypad bus: do not exceed 500 feet to keep auxiliary power
- 18-gauge keypad bus: do not exceed 1,000 feet
- Max distance from any module to the keypad bus is 1,000 feet; extend with a DMP 505-12 or DMP PS12-5
- Any one bus circuit max is 2,500 feet, one run or branches combined
- Max voltage drop from the panel or aux supply to any device is 2.0 VDC
- Keypad circuit max output is 2 A
- A 710 Bus Splitter/Repeater raises keypad wiring distance to 2,500 feet